Cable Shielding
Single-side connection to control electronics
Control Dynamics Adjustment
Switches S3.1-S3.6 for oil volume
Fault Indication
LED indicators on the front panel
Functional Testing
Use measuring sockets for input/output values
Operating Pressure Adjustment
Using potentiometer R2
Pressure Command Input
0...10 V
Pressure Controller Gain Settings
Switches S3.7-S3.8, Jumper 11
Pressure Limitation Feature
0...+100% with potentiometer R3
Pressure Transducer Connection
LiYCY 2 x 0.25 mm² cable
Pressure Transducer Range
0...315 bar
Protection Fuse Recommendation
1.6 A slow-blowing
Signal Adjustments Available
4...20 mA, 0...10 V
Swivel Angle Command
Measured at socket 3
Voltage Supply
24 V DC