Product Type
Mains Filter
Usage
Used with HMV and HCS converters
Protection Rating
IP 20 (as per DIN EN 60529)
Features
Suppression of leakage current, Scalable
Phases
Three-phase
Nominal Current Rating
202A
Design Code
1
Intended Operation Area
Category C3 industrial areas (as per DIN 61800-3)
Weight
29kg
Supply System
Type E
Tightening Torque (Input Terminals)
Maximum 30Nm
Max Cross-Sectional Area (Input Terminals)
150mm2 or AWG 5/0
Cooling Method
Natural convection
Insulation Resistance
1.18MOhms at 500VDC
Dimensions
150 x 440 x 262 mm (B x H x T)
Power Dissipation
Less than 238W
Maximum Drives Support
12.
We offer a repair service for the HNF01.1A-F240-E0202-A-480-NNNN.