Cooling Method: Forced Air Cooling
Permitted Ambient Temperature Range: 0 to 40 degrees Celsius
Drive Output Derate Rate: 2.5% per K (40-50 degrees Celsius)
Minimum Cooling Air Requirement: 0.03 cubic meters per second
Drive Power Loss: 0.33 kilowatts
Mounting: At the rear
Heat Sink Location: Inside or Outside the Enclosure
Compliance: Level A1 of EN 55011
AC Input Range: 380 to 480 Volts
Brake Chopper Continuous Power Rating: 3.8 kilowatts
Brake chopper Maximum Power: 18 kilowatts
Rated Output at 4kHz Pulse: 7.5 kilowatts
Rated Current Output at 4kHz Pulse: 18 Amps
Peak Current Output at 4kHz Pulse: 31 Amps
Rated Output at 8kHz Pulse: 5.5 kilowatts
Rated Current Output at 8kHz Pulse: 13 Amps
Peak Current Output at 8kHz Pulse: 26 Amps
Additional Function: 24 Volts Stand by Power
Firmware: Ordered Separately
Global Shipping: Yes