Or speak to a sales representative for additional information:
Product Type
Voltage-Frequency Converter
Required Supply Voltage
AC 500V (10% tolerance)
Power Source
3-phase
Built-In Brake Chopper
Yes
Weight (including brake chopper)
11.3 kg
Rated Motor Output
18.5 kW
Operating Ambient Temperature
0 to 40 degree Celsius
Required Input Current
28 A
Output Frequency
0 - 250 Hz
Rated Power
23 kVA
Peak Power (for 60 seconds)
30 kVA
Environmental Class
3K3
Air Required for Cooling
0.05 cubic meters per minute
Power Loss During Cooling
0.57 kW
Radio Suppression Immunity Class
A1
Protection Class
IP 20
External Stand-By Power (with starting lockout)
Yes