The Bosch Rexroth Indramat R-IB IL AI 2/SF-PAC from the R-IB Interface Modules series is a high-performance analog input module designed for Inline station applications in industrial automation. With an input voltage range of 0 … ±10 V and a measurement resolution of 16 bits, it delivers precise signal acquisition for critical process control. Weighing just 69 g and offering a process data update rate of under 1.5 ms, this module ensures rapid, accurate feedback for demanding control systems. It supports both current and voltage measurements, making it suitable for diverse sensor inputs.
Featuring two single-ended analog channels, the R-IB IL AI 2/SF-PAC accommodates three current ranges (0 … 20 mA, ±20 mA, 4 … 20 mA) and two voltage ranges (0 … 10 V, ±10 V), with each channel individually configurable via the bus. It connects to sensors using 2- and 3-wire technology and employs spring cage terminals for robust field wiring. The Inline data jumper offers seamless bus integration, while its dimensions of 12.2 x 135 x 71.5 mm optimize space in control cabinets. Operating reliably up to 500 kbaud transmission speed, this module maintains common mode rejection of 90 dB to minimize interference and ensure signal integrity in harsh environments.
Built to withstand temperatures from –25 °C to +55 °C (storage: –25 °C to +85 °C) and humidity levels up to 90% (non-condensing), the module features an IP20 protection category and meets Class 3 standards per VDE 0106 and IEC 60536. It complies with shock resistance per IEC 60068-2-27 and draws minimal power from the local bus (typ. 30 mA, max. 40 mA at 24 V DC) plus <882 mW total consumption, maximizing efficiency. With a compact form factor and industry-certified durability, the R-IB IL AI 2/SF-PAC enhances signal accuracy, speeds up response times, and reduces system complexity, delivering reliable performance for sophisticated industrial automation tasks.
Connection Type
Spring cage terminals
Dimensions (w X H X D)
12.2 x 135 x 71.5 mm
Input Current Range
0 ... 20 mA, ±20 mA, 4 ... 20 mA
Input Voltage Range
0 ... 10 V, ±10 V
Local Bus Connection Type
Inline data jumper
Max. Humidity
5 ... 90%, no condensation
Max. Temperature
-25 ... +55 °C
Measurement Resolution
16 bits
No. Wires In Connection
2 and 3
Peripheral Supply Voltage Uana
24 V DC
Power Consumption From Local Bus Ul Typ.
30 mA, max. 40 mA
Process Data Update
< 1.5 ms
Protection Category
IP20
Transmission Speed
500 kbaud
Weight
69 g