The Bosch Rexroth Indramat R-IB IL AO 2/U/BP-PAC is a high-precision analog output module in the R-IB Interface Modules series designed for Inline stations. Manufactured by Bosch Rexroth Indramat, this module provides 2 single-ended analog outputs capable of delivering both current ranges of 0 to 20 mA and voltage ranges from –10 to +10 V. Operating on a logic voltage of 7.5 V and protected to IP20 standards, it fulfills critical industrial requirements for accurate signal transmission and robust environmental protection in automated control systems.
This module features exceptional technical specifications tailored for demanding applications. With a resolution of 16 bits and a basic error limit of ±0.02%, it guarantees extremely stable and repeatable output signals. The process data update time of < 1 ms ensures rapid digital-to-analog conversion, while the transmission speed of 500 kbaud provides fast and reliable communication across the Inline station network. Actuator interfaces employ a 2-wire connection with shield grounding, supporting output loads from 0 to 500 Ω for current outputs and a minimum of 2 kΩ for voltage outputs. Peripheral and bus supply requirements are modest, with typical current draws of 33 mA (max. 40 mA) from the local bus (Ul) and 25 mA (max. 35 mA) from the 24 V DC auxiliary supply (Uana).
Built for industrial resilience, the module operates reliably across a temperature range of –25 °C to +55 °C and incorporates transient protection on analog outputs to mitigate electrical surges. The device supports shielded, twisted power station cables up to 500 meters for flexible system integration in large installations. Its low power consumption—peaking at 0.85 W under full load—minimizes heat generation and contributes to overall energy efficiency. By combining precision output, rapid response, and durable design, the R-IB IL AO 2/U/BP-PAC delivers significant benefits in automated manufacturing, process control, and motion applications where consistent analog signaling and long-term reliability are paramount.
Actuator Connection Type
2-wire connection
Analog Outputs
2 single-ended outputs
Basic Error Limit
±0.02%
Current Ranges
0 to 20 mA, 4 to 20 mA
Logic Voltage Ul
7.5 V
Output Load, Current Output
0 to 500 Ω
Output Load, Voltage Output
Min. 2 kΩ
Peripheral Supply Voltage Uana
24 V DC
Permissible Temperature (operation)
-25 to +55°C
Power Consumption From Local Bus Ul
Typ. 33 mA, max. 40 mA
Power Consumption From Uana
Typ. 25 mA, max. 35 mA
Process Data Update
< 1 ms
Resolution
16 bits
Transmission Speed
500 kbaud
Voltage Ranges
-10 to +10 V, 0 to +10 V